Bryant Evolution +95s Plus – Error 33, Hi Limit Trip (2024)

01-25-2016,10:02 PM #1

I own a Bryant Model 355CAV060100 natural gas furnace that was installed in my house in 2010 and worked well for 2-3 years and then occasionally/rarely indicated a failure on the Evolution thermostat. The LED on the circuit board would indicate Error 33. The filter was changed regularly and the registers were all open and unobstructed. The system would reset automatically and run fine. Over then next couple winters the problem would occur more often especially when it would get bitter cold outside. I was primarily using a wood stove along with the gas furnace as an auxiliary unit, therefore the repair was not urgent to maintain comfort.

The inducer would spin, the igniter would glow, the solenoid would switch on the gas and the burner would ignite, once the heat exchanger warmed up the blower would start, after a few minutes the unit would trip off for a few minutes and then the cycle would repeat.

I attempted troubleshooting the unit including: replace air filter, verify registers open/unobstructed, verified combustion air intake/exhaust piping is free of obstruction, cleaned condensate trap and drain lines, verified blower spins freely with firmly attached blower squirrel cage blades and nothing seemed abnormal. I purchased a manometer and checked the three-stage gas valve pressure and monitored the voltage to the solenoids with a digital volt meter. The input gas pressure and each Low/Med/High gas pressure settings were within specification. The solenoid 24V control signals controlled the valves and the gas pressure followed as expected (ie. not a stuck solenoid issue).

I found the limit switch was opening due to high heat condition in the heat exchanger. The flame roll-out switch was not open, and the manual reset was in a normal position (not requiring manual reset). I replaced both of these sensors with OEM parts because they were inexpensive and possibly the source of the fault. The problem was not resolved. I tried one cycle with the filter removed and the filter door open to provide plenty of air intake, with no change to the problem.

I modified the original hi limit switch to accommodate a thermometer and allow me to jumper/bypass the limit circuit. I first measured the temperature at which the limit switch opened, then with the limit circuit bypassed I measured the temperature and it continued to rise. I shut the furnace off manually once it reached maximum operating temperature to avoid a fire safety issue. This confirmed for me that the unit is not just running a little hot or the limit switch is a little out of spec, the system is not balancing the heat generated with the airflow around the heat exchanger.

I measured temperature rise to be 62 deg F when the unit shuts down on medium heat, this value is in spec however I don’t know if it reached a steady state temperature before shut down.

I opened the evaporator and inspected the coil for restricted airflow. The coil looked fairly clean and a flashlight easily shined thru. I used CRC coil cleaner to clean the evaporator while I had it open for inspection. This did not fix the issue. I measured the static pressure with a pressure probe and found it less than the maximum 0.5 inches H2O (med=0.1 and high fan speed=0.2 inches H2O).

I determined the unit uses an electronic control module to run the DC motor and not start/run capacitors that could affect the RPM of the blower motor. So a simple capacitor replacement is not an option for my unit.

I concluded that the issue is with either the thermostat, main circuit board, motor control module or the blower motor. These parts are too expensive to randomly replace. I then called the company who installed the system, they checked many of the same items that I verified/replaced. On the third service call the circuit board was swapped and the furnace now runs properly. I don’t know the exact circuit board failure mode, but assume the blower speed directed by the board was an incorrect slower speed than required.

I don’t have a question, I just wanted to share this overall experience as it may help others with similar issues.

Reply Reply With Quote

Bryant Evolution +95s Plus – Error 33, Hi Limit Trip (2024)

FAQs

Bryant Evolution +95s Plus – Error 33, Hi Limit Trip? ›

error 33 is a high limit fault. It CAN include the roll-out switches, but usually it is the high limit switch located inside the heat exchanger blower compartment. This tripping is mainly caused by either a clogged indoor air filter, or a failing indoor blower or blower component.

What is error code 33 on Bryant Plus 95s evolution? ›

BRYANT ERROR CODE 33

Indicates a limit or flame rollout, is open or the furnace is operating in high-heat only mode due to 2 successive low heat limit trips. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13.

What is error code 33 limit circuit fault? ›

Code 33 is a Limit Circuit Fault code. This means that the flame rollout switch is open. If the high limit or flame rollout switch is open, you will experience error code 13.

How do you reset a Bryant furnace? ›

They are located just outside the burner chamber. Turn off the power then press the small button between the 2 leads to reset it. If it clicks you have reset it and the unit will fire up when you turn the power back on with any luck.

How do I fix code 33? ›

Error 33 is likely the furnace is overheating. Please set your fan switch to on and see if the house fan comes on. If the house fan does not come on then you should look at the relay for the house fan. This can be found by tracing the fan circuit.

What is system error 33? ›

Code 33 “Windows cannot determinewhich resources are required for this device. (Code 33)”

What is 33 error in AC? ›

I have I carrier AC heater and its flashing 33 error code. It won't even try to start it does nothing. The 33 error is an open limit error code. (electrically), automatic reset, temperature-activated sensor.

What causes a limit circuit lockout? ›

If the temperature is too high or the pressure too low, the limit switch will close, instructing the furnace to shut down and enter lockout mode. A dirty filter may also cause the limit switch to trip by reducing the air flow.

What is the code 33 map sensor circuit error? ›

MAP Sensor Circuit Error (Signal High Indicating Low Vacuum)

Low voltage would indicate high engine vacuum and lower engine load. The ECM uses the information from this sensor to help calculate fuel delivery and spark timing.

How to tell if a limit switch is bad? ›

First, let's talk about the signs of a faulty furnace limit switch. One common sign is when your furnace doesn't turn on at all. Another sign is when it continuously cycles on and off without reaching the desired temperature.

How do you manually reset the limit switch on a furnace? ›

Find the 'limit switch'

Once you've opened the control panel, search for a red or yellow elevated switch or button near the ignition control box. Now all that is left is to push and release the limit switch to reset your furnace manually.

What triggers a limit switch in a furnace? ›

If the air inside your furnace gets too hot, the limit switch trips to prevent overheating. If the furnace high limit switch trips due to overheating, there is likely an airflow issue that is preventing proper air movement through the system. Check your air filter, and replace it if dirty.

What is code 33 on Bryant furnace? ›

How Do I Fix It? I have a Bryant furnace showing error code 33. This indicates that the filter needs to be changed - and it did (badly). Further on it says that the Furnace Rollout Switch and the BVSS require manual reset.

How to clear system malfunction on bryant evolution thermostat? ›

Follow These Steps To Reset Your Bryant Thermostat:

Locate the circuit breaker box and find the circuit breaker that is associated with your air conditioner unit. Then reset the circuit breaker for your air conditioner unit. Wait for 30 seconds to let the device calm down before turning the AC thermostat back on.

How do I read my Bryant furnace error code? ›

You can view the error code LED or display through a small, clear plastic inspection port in the centre of the lower furnace cover. If the control board isn't in the lower compartment, it's in the upper compartment.

What is error 33 on air conditioner? ›

The 33 error is an open limit error code. (electrically), automatic reset, temperature-activated sensor. conditioned air passing over the heat exchanger. blower and monitors heat exchanger compartment temperatures.

What is the E3 code on a Bryant thermostat? ›

Error type E3 means Thermostat is overheated, heating is turned off. Wait until thermostat cools down. The thermostat requires no restart, but will start heating when the temperature is lowered. This might indicate faulty installation or very high temperature setpoint.

What is error code 33 on inverter? ›

Event number 33 and the corresponding 4-digit event numbers indicate that the power supply at the DC input is not sufficient for stable operation of the inverter and the inverter therefore cannot connect to the utility grid yet.

Top Articles
Latest Posts
Article information

Author: Dr. Pierre Goyette

Last Updated:

Views: 5430

Rating: 5 / 5 (70 voted)

Reviews: 93% of readers found this page helpful

Author information

Name: Dr. Pierre Goyette

Birthday: 1998-01-29

Address: Apt. 611 3357 Yong Plain, West Audra, IL 70053

Phone: +5819954278378

Job: Construction Director

Hobby: Embroidery, Creative writing, Shopping, Driving, Stand-up comedy, Coffee roasting, Scrapbooking

Introduction: My name is Dr. Pierre Goyette, I am a enchanting, powerful, jolly, rich, graceful, colorful, zany person who loves writing and wants to share my knowledge and understanding with you.